Responsive Menu
Add more content here...
Ateva Technologies

Multi IR Flame Detector 3600-M

he 3600-M uses infrared (IR) technology, a reliable design that provides early warning of flaming fires and immunity to false alarms from IR sources such as sunlight and IR projectors.

The 3600-M utilizes a Multi-Spectrum Design, allowing it to detect hydrocarbon and hydrogen flames up to 215 feet away. It can detect a gasoline pan fire at 215 feet or a hydrogen flame at 100 feet in less than 5 seconds. Users can also select different sensitivity levels to ensure no other detectors cross-over detection zones. Other features include a heated window to eliminate condensation and icing, HART and Modbus capabilities for digital communications, low power requirements, and a compact design.

The Multi IR Flame Detector 3600-M is approved and certified by a variety of third party agencies, including FM, ATEX, IECEx, TUV, and CSA. These approvals and certifications assure our customers that we carry only the highest quality of products and performance.

1. MULTI-SPECTRUM DESIGN

Detect hydrocarbon and hydrogen flames up to 215 feet away

2. IR SENSITIVITY SELECTION

Choose between short and long distance sensitivity ranges, depending on the needs and function

3. 5-SECOND RESPONSE

Quickly respond and alarm users of a fire in a swift manner

4. HEATED WINDOW

Eliminate any possible condensation or icing to ensure the detector to function properly

5. LOW POWER REQUIREMENTS

Save energy costs while protecting the facility

6. MULTIPLE OUTPUT OPTIONS (RELAY OUTPUTS, 0-20 MA, HART, MODBUS RS-485)

Easily install in a variety of field applications and easily obtain critical safety information wherever needed with maximum flexibility and compatibility

Model Number 3600-M
Spectral Response Multi IR Bands
Detection Range (At highest Sensitivity Setting for 1 sq. ft. / 0.1 sq. m pan fire)

215 ft. (65 m) n-Heptane
215 ft. (65 m) Gasoline
150 ft. (45 m) Diesel F
150 ft. (45 m) JP5
100 ft. (30 m) Hydrogen
150 ft. (45 m) Kerosene
135 ft. (40 m) Ethanol
115 ft. (35 m) Methanol
135 ft. (40 m) IPA (Isopropyl Alcohol)
100 ft. (30 m) Methane*
100 ft. (30 m) LPG*
16 ft. (5 m) Polypropylene Pellets
33 ft. (10 m) Office Paper

*20” (0.5 m) high, 8” (0.2 m) with plume fire

Response Time Typically 5 seconds
Adjustable Time Delay Up to 30 seconds
Sensitive Range 4 Sensitive Ranges for 1 sq. ft. (0.1 sq. m) n-heptane pan fire from 50 ft. (15 m) to 215 ft. (65 m)
Field of View Gasoline: 67o horizontal, 70o vertical

Hydrogen: 80o horizontal, 80o vertical

Built-in-Test (BIT) Manual and Automatic
Temperature Range Operating: -67oF to 167oF (-55oC to 75oC)

Operating Option: -67oF to 185oF (-55oC to 85oC)

Storage: -67oF to 187oF (-55oC to 85oC)

Humidity Up to 95% non-condensing (withstands up to 100% RH for short periods)
Heated Options To eliminate condensation and icing on the window
Electrical Specifications Operating Voltage: 24 VDC nominal (18-32 VDC)

Power Consumption:

  • Standby: Max. 90 mA (110 mA with heated window)
  • Alarm: Max. 130 mA (160 mA with heated window)

Cable Entries: 2 x ¾” – 14 NPT conduits or 2 x M25 x 1.5 mm ISO

Wiring: 12 – 22 AWG (2.5 mm 2 – 0.3mm2)

Electrical Input Protection: According to MIL-STD-1275B

Electromagnetic Compatibility: EMI/RFI protected to EN61326-3 and EN61000-6-3

Electrical Interface: The detector includes twelve (12) terminals with five (5) wiring options (factory set)

Outputs Relays:

  • Alarm, Fault, and Auxiliary
  • SPST volt-free contacts rated 5A at 30 VDC or 250 VAC

4-20 mA (stepped)

 

  • Sink (source option) configuration
  • Fault: 0 + 1 mA
  • Warning: 16 mA +/- 5%
  • BIT Fault: 2 mA +/- 10%
  • Alarm: 20 mA +/- 5%
  • Normal: 4 mA +/- 10%§ Resistance Loop: 100-600 ohms

HART Protocol: Optional HART communication on the 0-20 mA analog current (FSK) – used for maintenance, configuration changes and asset management, available in mA source output wiring options RS-485: RS-485 Modbus compatible communication link that can be used in computer control installations

Mechanical Specifications Materials/Enclosure Options: Heavy-duty copper free aluminum (less than 1%), red epoxy enamel finish (ATEX Approval only)

Stainless Steel 316L with electro polish finish (FM or ATEX Approval)

Mounting: Stainless Steel 316L with electro polish finish

Dimensions:

  • Detector: 4” x 4.6” x 6.18” (101.6 x 117 x 157 mm)

Weight

  • Aluminum: 2.8 lb. (1.3 Kg)
  • Stainless Steel 316L: 6.1 lb. (2.8 Kg)
  • Tilt Mount: 2.2 lb. (1.0 Kg)

Environmental Standards: Meets MIL-STD-810C for Humidity, Salt & Fog, Vibration, Mechanical Shock , High Temp, Low Temp

Water and Dust: IP66 and IP67 per En60529, NEMA 250 6P

Approvals Hazardous Area

  • ATEX & IECEx

    Ex II 2 GD
    Ex de IIB + H2 T5 (-55o to 75oC)
    Ex de IIB + H2 T4 (-55o to 85oC)
    Ex tD A21 IP66/X7 T 95oC
    Ex tD A21 IP66/X7 T 105oC

  • FM/CSA

    Class I Div. 1, Groups, B, C & D
    Class II/III Div. 1, Groups E, F & G

Performance

  • EN54-10 (LPCB)
  • FM-3260 (FM)

Reliability

  • IEC61508 – SIL-2 (TUV)
  • PDO Approval: Petroleum Development Oman Certificate of Registration
  • ISO 9001:2008: Registered Quality System
Accessories Fire Simulator: 20/20-310

Tilt Mount: 3600-01

Weather Protector: 777163

Air Shield: 777650

Mini Laptop Kit: 777820

USB RS-485 Harness Kit: 794079-5

Laser Pointer (Detector Area Coverage): 777166